The calculation of the heating system of a private house: the steps of the calculation scheme

click fraud protection

Heating a private house is a necessary element of comfortable housing. Agree that the arrangement of the heating complex should be approached carefully, because mistakes are expensive. But you have never done such calculations and do not know how to perform them correctly?

We will help you - in our article we will examine in detail how the calculation of the heating system of a private house is done in order to effectively compensate for heat losses in the winter months.

Let us give concrete examples, adding material photos and useful video tips, as well as up-to-date tables with indicators and coefficients necessary for calculations.

The content of the article:

  • Heat loss of a private house
    • Calculation of heat loss through the walls
    • Accounting for the effects of ventilation of a private house
    • Energy costs for preparing DHW
  • Calculation of the power of the heating boiler
  • The choice of radiators
  • Conclusions and useful video on the topic

Heat loss of a private house

The building loses heat due to the difference in air temperature inside and outside the house. Heat loss is higher, the more significant the area of ​​enclosing structures of the building (windows, roof, walls, basement).

instagram viewer

Also heat loss associated with the materials of enclosing structures and their sizes. For example, the heat loss of thin walls is more than thick.

Image Gallery

A photo of

The heating system of a private house with two units

The main purpose of the calculation of heating is the competent choice of a heating unit that can compensate for heat loss during the cold period of the year.

The option of heating in a log house

To select the necessary power equipment, heat losses are accumulated through the building envelope.

Air intake and heat leakage through windows and doors

The calculations take into account the leakage of heat through the loosely fitting window sashes and door leafs, as well as the energy required for heating the incoming air

Ventilation system with fresh air supply

For rooms with organized mechanical ventilation, carrying out mixing of fresh air mass from the outside, the need for energy consumption for its heating is taken into account.

Diagram of the device for hot water supply and heating

If it is planned to use a double-circuit boiler as the main unit of heating and water heating for the DHW system, the energy necessary for this task is taken into account in the calculations.

Selection of the boiler by type of fuel

Competently performed calculations necessarily take into account the type of fuel and its energy efficiency.

Options for laying heating circuits

All calculations are adjusted with reference to the method of arrangement of heating circuits, with hidden installation of the system, consideration should be given to the heating of building structures.

Outdoor heating option

When calculating for an open heating scheme that communicates directly with the atmosphere through an open expansion tank, energy losses are necessarily taken into account when the coolant cools.

The heating system of a private house with two units

The heating system of a private house with two units

The option of heating in a log house

The option of heating in a log house

Air intake and heat leakage through windows and doors

Air intake and heat leakage through windows and doors

Ventilation system with fresh air supply

Ventilation system with fresh air supply

Diagram of the device for hot water supply and heating

Diagram of the device for hot water supply and heating

Selection of the boiler by type of fuel

Selection of the boiler by type of fuel

Options for laying heating circuits

Options for laying heating circuits

Outdoor heating option

Outdoor heating option

Effective heating calculation for a private house, it is necessary to take into account the materials used in the construction of walling.

For example, with equal thickness of a wall made of wood and brick, heat is conducted with different intensity - heat losses through wooden structures go slower. Some materials transmit heat better (metal, brick, concrete), others worse (wood, mineral wool, polystyrene foam).

The atmosphere inside the residential building is indirectly connected with the external air environment. The walls, window and door openings, the roof and the foundation in the winter transfer heat from the house to the outside, supplying cold instead. They account for 70-90% of the total heat loss of the cottage.

Heat loss to calculate the heating system of a private house

The walls, the roof, the windows and the doors all let the heat out in the winter. The imager will clearly show the leakage of heat

The constant leakage of thermal energy during the heating season also occurs through ventilation and sewage.

When calculating the heat loss of individual housing construction, these data are usually not taken into account. But the inclusion of heat loss through the sewer and ventilation systems in the general heat calculation of the house is the right solution.

Heat loss country house

Properly arranged heat insulation system can significantly reduce heat leakage passing through building structures, door / window openings

It is impossible to calculate the autonomous heating circuit of a country house without evaluating the heat loss of its enclosing structures. More precisely, it will not work determine the power of the heating boiler, sufficient to heat the cottage in the most fierce frosts.

Analysis of the actual consumption of thermal energy through the walls will allow you to compare the cost of boiler equipment and fuel with the cost of insulation of the enclosing structures.

After all, the more energy-efficient the house, i.e. the less heat it loses in the winter months, the lower the cost of purchasing fuel.

For proper calculation of the heating system will require coefficient of thermal conductivity common building materials.

Thermal conductivity of structural materials

Table of values ​​of thermal conductivity of various building materials, most often used when erected

Calculation of heat loss through the walls

Using the example of a conditional two-story cottage, we calculate heat losses through its wall structures.

Initial data:

  • square “box” with front walls 12 m wide and 7 m high;
  • in the walls of 16 openings, the area of ​​each 2.5 m2;
  • front wall material - solid brick ceramic;
  • wall thickness - 2 bricks.

Next, we will calculate the group of indicators, of which the total value of heat loss through the walls is formed.

Heat Resistance Indicator

To find out the heat transfer resistance index for a facade wall, it is necessary to divide the wall material thickness by its thermal conductivity coefficient.

For a number of construction materials, thermal conductivity data are presented in the images above and below.

Heat conductivity coefficient of insulation

For accurate calculations, the thermal conductivity coefficient of the heat-insulating materials used in construction is required.

Our conventional wall is built of ceramic brick, the coefficient of thermal conductivity - 0.56 W / m ·aboutWITH. Its thickness, taking into account the laying on the TsPR, is 0.51 m. Dividing the wall thickness by the thermal conductivity coefficient of a brick, we obtain the resistance to heat transfer of the wall:

0.51: 0.56 = 0.91 W / m2 × oWITH

The result of the division is rounded to two decimal places, there is no need for more accurate data on heat transfer resistance.

Exterior wall area

Since a square building was chosen as an example, the area of ​​its walls is determined by multiplying the width by the height of one wall, then by the number of external walls:

12 · 7 · 4 = 336 m2

So, we know the area of ​​the facade walls. But what about the openings of windows and doors, occupying together 40 m2 (2.5 · 16 = 40 m2a) front wall, do you need to take them into account?

Indeed, how to correctly calculate independent heating in a wooden house excluding heat transfer resistance of window and door structures.

How to calculate heat loss through the walls

The coefficient of thermal conductivity of thermal insulation materials used for insulation of load-bearing walls

If you need to calculate the heat loss of a large building or a warm house (energy efficient) - yes, taking into account the heat transfer coefficients of window frames and entrance doors when calculating will be correct.

However, for low-rise buildings IZHS constructed from traditional materials, door and window openings can be neglected. Those. do not take away their area from the total area of ​​the facade walls.

Total wall heat loss

We find out the heat loss of the wall from its one square meter at a difference of one and two degrees inside and outside the house.

To do this, we divide the unit by the heat transfer resistance of the wall, calculated earlier:

1: 0.91 = 1.09 W / m2·aboutWITH

Knowing the heat loss from the square meter of the perimeter of the external walls, one can determine the heat loss at certain street temperatures.

For example, if the temperature in a cottage is +20 aboutC, and on the street -17 aboutC, the temperature difference will be 20 + 17 = 37 aboutWITH. In this situation, the total heat loss of the walls of our conditional home will be:

0.91 · 336 · 37 = 11313 W,

Where: 0.91 - heat transfer resistance per square meter wall; 336 - the area of ​​the front walls; 37 - the temperature difference between room and outdoor atmosphere.

Thermal insulation materials - thermal conductivity

Heat conductivity coefficient of heat-insulating materials used for floor / wall insulation, for dry floor screeding and leveling walls

Let us recalculate the obtained value of heat losses in kilowatt-hours, they are more convenient for perception and subsequent calculations of the power of the heating system.

Wall heat loss in kilowatt-hours

First, find out how much heat energy goes through the walls in one hour at a temperature difference of 37 aboutWITH.

We remind you that the calculation is carried out for a house with design characteristics that are conditionally selected for demonstration and demonstration calculations:

11313 · 1: 1000 = 11.313 kW · h,

Where: 11313 is the heat loss value obtained earlier; 1 hour; 1000 is the number of watts per kilowatt.

Thermal conductivity of building materials and thermal insulation

The coefficient of thermal conductivity of building materials used for wall and ceiling insulation

To calculate the heat loss per day, the resulting value of heat loss per hour is multiplied by 24 hours:

11.313 · 24 = 271.512 kW · h

For clarity, let's find out the heat loss for the full heating season:

7 · 30 · 271.512 = 57017.52 kW · h,

Where: 7 - the number of months in the heating season; 30 - the number of days in the month; 271,512 - daily heat loss of the walls.

So, the calculated heat loss from a house with the above-chosen characteristics of the building envelope will be 57017.52 kWh for the seven months of the heating season.

Accounting for the effects of ventilation of a private house

Calculation of ventilation heat losses during the heating season as an example will be carried out for a conditional cottage of square shape, with a wall 12 meters wide and 7 meters high.

Excluding furniture and interior walls, the internal volume of the atmosphere in this building will be:

12 · 12 · 7 = 1008 m3

At air temperature +20 aboutC (norm in the heating season) its density is equal to 1.2047 kg / m3and the specific heat 1,005 kJ / (kg ·aboutWITH).

Calculate the mass of the atmosphere in the house:

1008 · 1.2047 = 1214.34 kg,

Where: 1008 - the volume of the home atmosphere; 1.2047 - air density at t +20 aboutWITH .

Table of thermal conductivity of related materials

The table with the value of the coefficient of thermal conductivity of materials that may be required when carrying out accurate calculations

Suppose a fivefold change of air volume in the premises of the house. Note that the exact supply demand fresh air depends on the number of tenants of the cottage.

With an average temperature difference between the house and the street during the heating season, equal to 27 aboutC (20 aboutWith home, -7 aboutFrom the external atmosphere) for the day for heating the incoming cold air need thermal energy:

5 · 27 · 1214.34 · 1,005 = 164755,58 kJ,

Where: 5 - the number of air changes in the premises; 27 - temperature difference between room and street atmosphere; 1214.34 - air density at t +20 aboutWITH; 1,005 - specific heat of air.

We translate kilojoules to kilowatt-hours, dividing the value by the number of kilojoules per kilowatt-hour (3600):

164755.58: 3600 = 45.76 kWh

Having found out the cost of thermal energy for heating the air in the house when it is replaced five times through fresh air ventilation, it is possible to calculate the “air” heat losses during the seven-month heating season:

7 · 30 · 45.76 = 9609.6 kW · h,

Where: 7 - the number of "heated" months; 30 is the average number of days in a month; 45.76 - the daily cost of thermal energy for heating the supply air.

Ventilation (infiltration) energy costs are inevitable, since the renewal of air in the rooms of the cottage is vital.

The heating needs of a replaceable air atmosphere in a house need to be calculated, summed up with heat loss through walling structures and taken into account when choosing a heating boiler. There is another type of thermal energy, the latter - sewer heat loss.

Energy costs for preparing DHW

If during warm months cold water comes from the tap to the cottage, then during the heating season it is ice cold, with a temperature no higher than +5 aboutWITH. Bathing, washing dishes and washing impossible without heating water.

The water collected in the toilet tank contacts through the walls with the home atmosphere, taking some heat. What happens to the water heated by burning not free fuel and spent on domestic needs? It is drained into the sewer.

Boiler with boiler

Dual-circuit boiler with indirect heating boiler, used both for heating the heat carrier and for supplying hot water to the circuit built for it

Consider an example. A family of three, suppose it consumes 17 m3 water monthly. 1000 kg / m3 - the density of water, and 4,183 kJ / kg ·aboutC is its specific heat.

The average temperature of heating water intended for domestic needs, let it be +40 aboutWITH. Accordingly, the difference of the average temperature between the cold water entering the house (+5 aboutC) and heated in a boiler (+30 aboutC) it turns out 25 aboutWITH.

For the calculation of sewage heat loss we consider:

17 · 1000 · 25 · 4.183 = 1777775 kJ,

Where: 17 - the monthly volume of water consumption; 1000 is the density of water; 25 - temperature difference between cold and heated water; 4.183 — specific heat capacity of water;

To convert kilojoules to clearer kilowatt hours:

1777775: 3600 = 493.82 kWh

Thus, for the seven-month period of the heating season, the thermal energy in the amount of:

493.82 · 7 = 3456.74 kW · h

The consumption of thermal energy for heating water for hygienic needs is small compared to heat loss through walls and ventilation. But this, too, energy costs, loading the heating boiler or boiler and causing fuel consumption.

Calculation of the power of the heating boiler

The boiler in the heating system is designed to compensate for the heat loss of the building. And also, in the case of dual circuit system or at equipment of a boiler with a boiler of indirect heating, for water heating for hygienic needs.

Having calculated the daily heat losses and the flow of warm water “to the sewage system”, it is possible to accurately determine the required boiler capacity for a cottage of a certain area and the characteristics of the building envelope.

Boiler

Single-circuit boiler produces only the heating medium heating for the heating system

To determine the power of the heating boiler, it is necessary to calculate the cost of heat energy at home through the facade walls and to heat the alternating air atmosphere in the interior.

Required data on heat loss in kilowatt-hours per day - in the case of a conditional house, calculated as an example, is:

271.512 + 45.76 = 317.272 kWh,

Where: 271,512 - daily heat losses by external walls; 45.76 - daily heat losses for heating the supply air.

Accordingly, the required heating capacity of the boiler will be:

317.272: 24 (hours) = 13.22 kW

However, such a boiler will be under a constantly high load, reducing its service life. And in especially frosty days, the calculated boiler capacity will not be enough, since with a high temperature difference between the room and street atmospheres the building heat loss will sharply increase.

therefore choose a boiler on average calculation of the cost of heat energy is not worth it - it can not cope with severe frosts.

It would be rational to increase the required power of the boiler equipment by 20%:

13.22 · 0.2 + 13.22 = 15.86 kW

To calculate the required power of the second circuit of the boiler, heating water for washing dishes, bathing, etc. it is necessary to divide the monthly heat consumption of “sewer” heat losses by the number of days in a month and by 24 hours:

493.82: 30: 24 = 0.68 kW

According to the results of calculations, the optimal boiler power for an example cottage is 15.86 kW for the heating circuit and 0.68 kW for the heating circuit.

The choice of radiators

Traditionally heating radiator power It is recommended to choose by the area of ​​the heated room, and with 15-20% overestimation of power needs, just in case.

For example, consider how correct the method of selecting a radiator "10 m2 of area - 1.2 kW".

Ways to connect radiators

Thermal power of radiators depends on the method of their connection, which must be taken into account when calculating the heating system

Baseline: corner room on the first level of a two-story house IZHS; outer wall of double-row masonry ceramic bricks; room width 3 m, length 4 m, ceiling height 3 m.

Under a simplified selection scheme, it is proposed to calculate the area of ​​the room, we consider:

3 (width) · 4 (length) = 12 m2

Those. the necessary power of the heating radiator with a 20% surcharge is 14.4 kW. And now we calculate the power parameters of the heating radiator on the basis of the heat loss of the room.

In fact, the area of ​​the room affects the loss of heat energy less than the area of ​​its walls, going out one side to the outside of the building (facade).

Therefore, we will consider exactly the area of ​​"street" walls in the room:

3 (width) · 3 (height) + 4 (length) · 3 (height) = 21 m2

Knowing the area of ​​the walls that transmit heat "to the street", we calculate the heat loss when the difference between room and outdoor temperature is 30about (in the house +18 aboutC, outside -12 aboutC), and immediately in kilowatt-hours:

0.91 · 21 · 30: ​​1000 = 0.57 kW,

Where: 0.91 - heat transfer resistance m2 room walls, facing the street; 21 - the area of ​​"street" walls; 30 - temperature difference inside and outside the house; 1000 is the number of watts in kilowatts.

Installation of radiators

According to building standards, heating devices are located in places of maximum heat loss. For example, radiators are installed under window openings, heat guns - over the entrance to the house. In the corner rooms, the batteries are installed on blank walls exposed to the maximum exposure to winds.

It turns out that to compensate for heat losses through the facade walls of this structure, at 30about the temperature difference in the house and on the street is enough heating capacity of 0.57 kW · h. Increase the required power by 20, even by 30% - we get 0.74 kWh.

Thus, the actual power needs of heating can be significantly lower than the “1.2 kW per square meter of the floor space” trading scheme.

Moreover, the correct calculation of the required power of heating radiators will reduce the volume heating medium in the heating system, which will reduce the load on the boiler and fuel costs.

Conclusions and useful video on the topic

Where the heat leaves the house - the answers are provided by a visual video:

The video describes the procedure for calculating the heat loss at home through enclosing structures. Knowing the heat loss, you can accurately calculate the power of the heating system:

Detailed video about the principles of selection of power characteristics of the heating boiler, see below:

Heat generation annually rises in price - rising fuel prices. And the heat is constantly not enough. It is impossible to treat indifferently to the energy consumption of the cottage - it is completely unprofitable.

On the one hand, each new heating season is more expensive and more expensive for a homeowner. On the other hand, weatherization of the walls, the foundation and the roof of a country house costs good money. However, the less heat leaves the building, the cheaper it will be to heat it..

Preservation of heat in the premises of the house - the main task of the heating system in the winter months. The choice of power of the heating boiler depends on the state of the house and the quality of the insulation of its enclosing structures. The principle of "kilowatt per 10 squares of area" works in the cottage of the average condition of the facades, roofing and basement.

Did you independently calculate the heating system for your home? Or noticed the inconsistency of the calculations given in the article? Share your practical experience or the amount of theoretical knowledge, leaving a comment in the block under this article.

House foundation ventilation: when is it needed and how to equip it correctly

House foundation ventilation: when is it needed and how to equip it correctlyDesign And CalculationsVentilation

The duration of the building's operation is directly related to the start of its construction. Correctly mounted ventilation in the foundation of the house will prevent the destruction of floor and...

Read More
Ventilation from plastic sewer pipes in a private house: is it possible to do this + the nuances of arrangement

Ventilation from plastic sewer pipes in a private house: is it possible to do this + the nuances of arrangementDesign And CalculationsVentilation

Each living space must be equipped with a ventilation system, otherwise the owners will be faced with mold, mildew, dustiness and dampness. The microclimate in the house is far from optimal, and wi...

Read More
Ventilation in the dressing room: the best options and schemes for arranging the air exchange system

Ventilation in the dressing room: the best options and schemes for arranging the air exchange systemDesign And CalculationsVentilation

Have you planned the construction of a comfortable bath? Have you already built it, but have not decided on the ventilation? We will tell you about how the air exchange in the dressing room should ...

Read More
Instagram story viewer